Learn quickly with our PLC Training DVD Series: on sale $599.00 $379
Click here now for details!
Response
Time Concerns
Now
that we know about response time, here's what it really means to the
application. The PLC can only see an input turn on/off when it's looking.
In other words, it only looks at its inputs during the check input status
part of the scan.

In
the diagram, input 1 is not seen until scan 2. This is because when
input 1 turned on, scan 1 had already finished looking at the inputs.
Input 2 is not seen until scan 3. This is also because when the input
turned on scan 2 had already finished looking at the inputs.
Input 3 is never seen. This is because when scan 3 was looking at the
inputs, signal 3 was not on yet. It turns off before scan 4 looks at
the inputs. Therefore signal 3 is never seen by the plc.

|
To avoid this we say that the
input should be on for at least 1
input delay time + one scan time.
|
But
what if it was not possible for the input to be on this long? Then the
plc doesn't see the input turn on. Therefore it becomes a paper weight!
Not true... of course there must be a way to get around this. Actually
there are 2 ways.
Pulse stretch function.
This function extends the length of the input signal until the
plc looks at the inputs during the next scan.( i.e.
it stretches the duration of the pulse.)
|
 |
Interrupt function. This
function interrupts the scan to process a special routine that
you have written. i.e. As soon as the input turns on, regardless
of where the scan currently is, the plc immediately stops what
its doing and executes an interrupt routine. (A
routine can be thought of as a mini program outside of the main
program.) After its done executing the interrupt routine,
it goes back to the point it left off at and continues on with
the normal scan process.
|
 |
Now
let's consider the longest time for an output to actually turn on. Let's
assume that when a switch turns on we need to turn on a load connected
to the plc output.
The diagram below shows the longest delay (worst
case because the input is not seen until scan 2) for the output
to turn on after the input has turned on.
The maximum delay is thus 2 scan cycles
- 1 input delay time.

It's
not so difficult, now is it ?
Learn quickly with our PLC Training DVD Series: on sale $599.00 $379
Click here now for details!
Home
Previous Contents
Next